Part 2: The Different Types of Emergency Lighting
Designing a compliant emergency lighting scheme is about more than just placing a few exit signs above doors. It requires a clear understanding of the different types of emergency lighting available and where each one should be used.
Whether you’re planning a CAT A office fit-out or designing a bespoke commercial interior, it’s essential to get this right. The safety of a building’s occupants depends on it. But aesthetics matter too, especially when emergency fittings need to complement high-end finishes and architectural lighting schemes.
In this article, we break down the different categories of emergency lighting, what they do, and how they’re typically applied — so you can confidently specify or install the right type in the right location.
Understanding Emergency Lighting Categories
Emergency lighting falls into a few key categories, each serving a distinct purpose during a mains power failure. The main types are:
- Escape Route Lighting
- Open Area (Anti-Panic) Lighting
- High-Risk Task Area Lighting
- Standby Lighting
Let’s look at each in more detail.
Escape Route Lighting: The Backbone of Emergency Planning
This is the most familiar form of emergency lighting — typically what people think of when they hear “emergency light.” It’s designed to clearly illuminate escape routes such as corridors, stairwells, and doors, guiding occupants safely out of the building in an emergency.
Fittings must be placed to avoid any dark spots along the escape route, with at least 1 lux of light measured at floor level along the centre line of the path. Emergency exit signs with directional arrows also form part of this system.
Where to use it:
- Hallways
- Stairwells
- Fire exits
- Junctions and changes in direction
Open Area (Anti-Panic) Lighting: Preventing Confusion in Large Spaces
In open-plan offices, atriums, or large retail environments, people may panic if the lights go out, especially without a clear direction to an exit. That’s where open area lighting comes in.
Its purpose is to reduce panic by providing enough general illumination for occupants to see their surroundings and move safely toward an escape route. The required minimum is 0.5 lux across open floor areas.
Where to use it:
- Open-plan offices
- Reception areas
- Retail floors
- Breakout zones or canteens
High-Risk Task Area Lighting: Protecting People in Dangerous Zones
Some areas involve machinery, chemicals, or potentially hazardous equipment that could pose a threat during a power outage. High-risk task area lighting ensures enough illumination for people to safely shut down dangerous processes or evacuate safely.
This type of lighting must deliver higher light levels, typically 10% of the normal lighting levels in that area.
Where to use it:
- Manufacturing areas
- Laboratories
- Kitchens with industrial equipment
- Maintenance zones
Standby Lighting: Maintaining Operations (Optional)
Unlike the other categories, standby lighting isn’t a legal requirement. However, it’s often specified in mission-critical environments to maintain a level of functionality after the mains power fails.
This lighting doesn’t necessarily guide people out — it’s there to allow continued operation of systems or to complete vital tasks safely until the mains are restored.
Where to use it:
- Control rooms
- Data centres
- Hospitals
- Financial institutions
Maintained vs Non-Maintained Emergency Lights
Once you’ve selected the appropriate type of lighting, there’s another key decision: whether the lights are maintained or non-maintained.
- Maintained fittings stay on at all times, including during a power failure. They’re often used in public spaces like cinemas or shops where the lights form part of the general lighting.
- Non-maintained fittings only switch on when the mains power fails. These are typical for office environments, where emergency fittings shouldn’t be visible during normal operation.
There’s also a hybrid known as sustained lighting, which uses dual circuits to allow both maintained and non-maintained operation, although it’s less common.
Making the Right Choice for Your Project
Specifying the right type of emergency lighting isn’t just about compliance — it’s about designing for the specific use case of the building. A warehouse with moving equipment needs a different approach than a co-working space with open-plan desks and a design-conscious fit-out.
At Synergy, we offer a wide range of architectural-grade emergency lighting options — including recessed, surface, suspended, and LED linear options — many of which can be integrated seamlessly with the wider lighting scheme.
In part 3, we’ll explore the regulations and standards you need to meet — including BS 5266-1 and EN 1838 — and how to ensure full compliance without compromising on design.